
ATI A15/66 Residual Sulfite Monitor
27
O&M Manual
Rev-W (8/10)
PULSE FREQUENCY MODULATION (PFM) CONTROL
Relays A and B in the electronic monitor can be used for direct control of certain kinds of
metering pumps using a pulse frequency control mode. In pulse frequency control, the relay will briefly
close at a frequency linearly proportional to the deviation of the measured value from your setpoint. This
type of output is used when controlling a chemical metering pump that has a pulse frequency input from
an unpowered relay. To use PFM control, the relay must be configured for PFM control in steps 14 or 16
of the configuration menu. For chemical feed control, you will normally want to set the alarm relays to low
in steps 15 and 17.
To set up a control system using PFM control, you must program a setpoint, a proportional band,
and a frequency range. The setpoint is the maximum value that you would want to maintain. When the
measured value reaches the setpoint, the output frequency will stop. To set the setpoint, press the
MODE key until the display reads “SA X.XX PPM F L”. Then press the CAL key once. The display
will read “CAL SA S: X.XX”. Use the UP and DOWN keys to select the desired setpoint. Then press
ENTER.
The next setting is the proportional band setting. After pressing ENTER in the previous section,
the display will indicate “CAL SA BP: X.XX”. The proportional band is the amount of deviation from the
setpoint required for the frequency output to reach maximum pulses per minute. Use the UP and DOWN
keys to select the proportional band and then press ENTER.
The final setting is the maximum pulse frequency required to control the pump. You should check
your chemical feed pump manual to determine what overall frequency is recommended. The monitor can
be adjusted for full scale frequency outputs from 0-120 pulses per minute. When you press ENTER in the
previous step, the display will change to “CAL SA f: 100 i/m” This is the default setting of 0-100 pulses
per minute. Left at this value, the relay will pulse at 100 times per minute when the measured value at
maximum deviation from the setpoint and will not pulse at all when the measured value reaches the
setpoint. Enter the value you want for the maximum pulses per minute and press ENTER. The display
will flash UPDATE and the relay will begin to operate in accordance with the programming entered.
As an example, assume that you want to use relay A to control a metering pump feeding sodium
bisulfite. You would like to maintain a sulfite value between 0.5 and 1.0 PPM and your metering pump
input is 0-60 pulses per minute. Programming would then be as follows.
1. In the configuration menu, step 14, select PFM.
2. In the configuration menu, step 15, select LO
3. Go to the A relay display (display D4, page 20) and press CAL.
4. Adjust the setpoint value to 1.00 and press ENTER.
5. Adjust the proportional band value to 0.50 and press ENTER
6. Adjust the frequency to 60 and press ENTER.
With the programming just entered, relay A will pulse 60 times per minute when the measured
sulfite value is below 0.50 PPM. When the value reaches 0.75 PPM, the relay will be pulsing 30 times
per minute. When the value reaches 1.00 PPM, the relay will stop pulsing.
You can verify the operation of the relay by placing the monitor into simulate (SIM) mode of
operation. By manually increasing or decreasing the displayed value, you will hear the change in the
relay pulses. Note that the “” symbol indicating the relay condition will pulse each time the relay closes.
Komentarze do niniejszej Instrukcji